12kv High Voltage Switch Board/Distribution Switchgear/Distrubution Cabinet

1.General      This indoor metal-clad withdrawable switchgear(hereinafter short as switchgear)is a complete power distribution device for 3.6~24kV,3-phase AC 50Hz,single-bus and single-bus sectionalized system&p

Technical Feature

  • Shanghai, China
  • 50000unit/Year
  • L/C, T/T, D/P
Send Standard Inquiry Add Inquiry List

0 Add Favorite

$1~30

PRIMARY PARAMETERS

Model NO.
HS
Structure
Protection
Form
Partly-welded Type
Size
1 Uint
Shell Material
Stainless Steel
Brand
Shanghai Electric
Transport Package
Standard Export Package
Origin
Shanghai
Type
Power
Certification
ISO9001
Operation Voltage
High Voltage
Application Range
High-rise Buildings
Shell Protection Grade
IP23
Trademark
Shanghai Electric
Specification
type tested
HS Code
85372090

DETAIL DESCRIPTION

1.General
      This indoor metal-clad withdrawable switchgear(hereinafter short as switchgear)is a complete power distribution device for 3.6~24kV,3-phase AC 50Hz,single-bus and single-bus sectionalized system. It is mainly used for power transmission of middle/small generators in power plants; power receiving, transmission for substations in power distribution and power system of factories, mines and enterprises, and starting of large high-voltage motor, etc.,so as to control, protect and monitor the system. The switchgear meets IEC298,GB3906-91.In addition to be used with domestic VS1 vacuum circuit breaker, it can also be used with 3AH5 from Siemens domestic ZN65A,and VB2 from GE, etc.,it is truly a power distribution device with good performance.
      In order to meet the requirement for wall mounting and front-end maintenance, the switchgear is equipped with a special current transformer, so that the operator can maintain and inspect it in front of the cubicle.
2.Service environment
    a) Air temperature: Maximum temperature: +40°C; Minimum temperature:-15°C
    b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
    c) Altitude above sea level: Maximum installation altitude: 1000M.
    d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
    e) No frequent violent shake
 3.Main technical specifications
NoItemUnitParameter
1Rated voltagekV7.2kV, 12 kV,17.5kV,24kV
2Rated frequencyHz50/60
3Rated currentA630,1250,1600,2000,2500,3150,4000
4Branch busbar Rated currentA630,1250,1600,2000,2500,3150,4000
5Main busbar Rated currentA630,1250,1600,2000,2500,3150,4000
61min Power frequency
withstand voltage
wetkV3850/60
drykV4860/65
7Lightning impulse withstand voltagekV7595/125
8Rated short circuit breaking current (peak)kA40/50/63/80/100
9Short time withstand current(4s)kA20/25/31.5/40
10Protection type IP4X for housing

Send Consultations Sending PUBLIC question and getting response from the supplier